Air movement preferences observed in office buildings
690
Air Movements
Databases, Factual
Data Collection
Air motion
Sensation
Temperature
0211 other engineering and technologies
02 engineering and technology
Air movement preference
Ventilation
13. Climate action
Natural ventilation
Air Pollution, Indoor
11. Sustainability
Humans
Draft
Seasons
Workplace
Building Codes
DOI:
10.1007/s00484-006-0079-y
Publication Date:
2007-01-18T12:02:03Z
AUTHORS (7)
ABSTRACT
Office workers' preferences for air movement have been extracted from a database of indoor environmental quality surveys performed in over 200 buildings. Dissatisfaction with the amount of air motion is very common, with too little air movement cited far more commonly than too much air movement. Workers were also surveyed in a detailed two-season study of a single naturally ventilated building. About one-half the building's population wanted more air movement and only 4% wanted less. This same ratio applied when the air movement in workspaces was higher than 0.2 m/s, the de facto draft limit in the current ASHRAE and ISO thermal environment standards. Preference for "less air motion" exceeded that for "more" only at thermal sensations of -2 (cool) or colder. These results raise questions about the consequences of the ASHRAE and ISO standards' restrictions on air movement, especially for neutral and warm conditions.