Integrated energy performance modeling for a retail store building
Building envelope
Absorption refrigerator
DOI:
10.1007/s12273-013-0109-8
Publication Date:
2013-03-13T15:56:35Z
AUTHORS (7)
ABSTRACT
This paper presents an integrated energy performance modeling approach that considers heat and mass transfer through building envelope, HVAC (heating, ventilation, and air conditioning) and refrigeration systems of a retail store building with limited measured data. The internal heat gains/losses were estimated based on an Extended Kalman Filter. The simulation coupling strategy among room top units (RTUs), refrigeration display cases and zones is based on the ping-pong coupling strategy. The integrated model was validated against measured data from June to August, 2011. The results show that temperature prediction is within the ±1.5°C error band and the RTU electricity energy use prediction is within the ±10% error band. The difference between measured and simulated annual electricity consumption from the refrigeration system is 3%. Based on further analysis and diagnostics, deviations of model predictions from measured data were found to be partially due to the faults in the RTUs. Such deviation accounts for a 4% saving of the total building electrical energy consumption.
SUPPLEMENTAL MATERIAL
Coming soon ....
REFERENCES (22)
CITATIONS (13)
EXTERNAL LINKS
PlumX Metrics
RECOMMENDATIONS
FAIR ASSESSMENT
Coming soon ....
JUPYTER LAB
Coming soon ....