Experimental comparison between R152a and R134a working in a refrigeration facility equipped with a hermetic compressor

0211 other engineering and technologies 02 engineering and technology 7. Clean energy R134a Hermetic compressor GWP R152a 13. Climate action MAQUINAS Y MOTORES TERMICOS F-gas Internal heat exchanger
DOI: 10.1016/j.ijrefrig.2015.06.021 Publication Date: 2015-07-30T00:50:24Z
ABSTRACT
The EU Regulation 517/2014 has recently been approved in a further attempt to curb the effects of Global Warming. As a consequence, the refrigeration sector is moving towards refrigerants with a low Global Warming Potential (GWP100) in accordance with the limit fixed by these regulations (150). In this regard, the old refrigerant R152a attracts renewed interest due to its low GWP (138) and its similarity to R134a. The present work shows the results of using R152a in a vapour compression plant equipped with a hermetic compressor and an IHX designed for R134a. The refrigerant was replaced by a conventional “drop-in” process in order to carry out an energy comparison. The results have revealed an improvement in the COP with R152a up to 13% despite a reduction in the cooling capacity of about 10%. During the test campaign, R134a hermetic compressors have been shown to be capable of operating with R152a. The authors acknowledge Jaume I University of Spain, who financed partially the present study through the research project P1⋅B2013-10.
SUPPLEMENTAL MATERIAL
Coming soon ....
REFERENCES (22)
CITATIONS (62)