Contingency-constrained unit commitment with post-contingency corrective recourse

FOS: Computer and information sciences Computer Science - Computer Science and Game Theory Optimization and Control (math.OC) FOS: Mathematics Mathematics - Optimization and Control Computer Science and Game Theory (cs.GT)
DOI: 10.1007/s10479-014-1760-x Publication Date: 2014-12-04T07:56:09Z
ABSTRACT
We consider the problem of minimizing costs in the generation unit commitment problem, a cornerstone in electric power system operations, while enforcing an N-k-e reliability criterion. This reliability criterion is a generalization of the well-known $N$-$k$ criterion, and dictates that at least $(1-e_ j)$ fraction of the total system demand must be met following the failures of $k$ or fewer system components. We refer to this problem as the Contingency-Constrained Unit Commitment problem, or CCUC. We present a mixed-integer programming formulation of the CCUC that accounts for both transmission and generation element failures. We propose novel cutting plane algorithms that avoid the need to explicitly consider an exponential number of contingencies. Computational studies are performed on several IEEE test systems and a simplified model of the Western US interconnection network, which demonstrate the effectiveness of our proposed methods relative to current state-of-the-art.
SUPPLEMENTAL MATERIAL
Coming soon ....
REFERENCES (37)