Experimental investigation of a mini-type solar absorption cooling system under different cooling modes
Chilled water
Absorption refrigerator
Chiller
Fan coil unit
Radiant cooling
Cooling capacity
DOI:
10.1016/j.enbuild.2011.11.036
Publication Date:
2011-12-07T19:44:22Z
AUTHORS (5)
ABSTRACT
Abstract Solar absorption cooling systems are available from various reports, in large capacities up to several hundred kilowatts. However, in the range of small capacities ( 2 solar collector arrays, one absorption chiller with a rated cooling capacity of 8 kW, and a hot storage water storage tank of 3 m 3 in volume. The chilled water can be delivered either into fan coils or into radiant cooling panels, which are installed to satisfy the demands of the indoor thermal environment of the test room. As for the fan coil cooling mode, it was found that the average cooling output reached 4.27 kW during 9 h of operation under typical weather conditions for Shanghai. The PMV (predicted mean value, a measure of thermal comfort) inside the test room could be controlled between −0.29 and 0.32. With regard to the radiant cooling mode, an individual supply air unit was installed for the purpose of preventing condensation on the cooling panels. Comparing with the experimental results of the fan coil cooling mode, the average cooling output increased by 23.5%.