Lightning performance of transmission lines: Assessing the quality of traditional methodologies to determine backflashover rate of transmission lines taking as reference results provided by an advanced approach

Lightning Line (geometry)
DOI: 10.1016/j.epsr.2017.01.005 Publication Date: 2017-01-12T03:03:10Z
ABSTRACT
Abstract This paper presents a critical review of CIGRE and IEEE traditional methodologies for calculating the backflashover outage rate (BFOR) of transmission lines, considering their adopted simplifications. These methodologies, along with an advanced computational approach named HEM-DE, were applied to a real 138-kV line to determine its backflashover rate. The quality of the results produced by the methodology at each step of their calculation procedure was assessed and discussed, taking as reference the accurate results provided by the advanced approach, based on the application of the hybrid electromagnetic model (HEM) and disruptive effect model (DE). According to this assessment, in the 40-to-10-Ω range of tower footing grounding resistance, the CIGRE methodology overestimates outage rate of the line in relation to the reference values (98–21% larger in the 40-to-10-Ω range of tower footing grounding resistance). The IEEE methodologies underestimates the BFOR, yielding rates 47–23% lower in the same resistance range.
SUPPLEMENTAL MATERIAL
Coming soon ....
REFERENCES (20)
CITATIONS (14)